|
Utilities
Department Home |
| Backflow Regulations |
|
§35-44. Definitions
(A) Air Gap - The unobstructed vertical distance through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture, or other device and the flood level rim of the receptor. (B) Atmospheric Vacuum Breaker - A device which prevents back-siphonage by creating an atmospheric vent when there is a negative pressure in a water system, and not subject to static line pressure. (C) Auxiliary Water Supply - Any water supply system on or available to the premises other than the City's approved public potable water supply system. (D) Backflow - The reversal of designed flow in a potable water system. (E) Backflow Preventer - An assembly or means that prohibits the backflow of water into the potable water supply. (F) Backpressure - A pressure, higher than the supply pressure, caused by a pump, elevated tank, air/stream pressure, or any other means, which may cause backflow. (G) Back-siphonage - Backflow caused by negative or reduced pressure in the supply piping. (H) Cross-connection - Any arrangement whereby contamination or pollution due to backflow, backpressure, or back-siphonage can occur. (I) Double Check Valved Assembly - An assembly of two (2) independently operating spring loaded check valves with tightly closing shut-off valves on each side of the check valves, plus properly located test cocks for the testing of each check valve. (J) Pressure Vacuum Breaker - A device containing one or two independently operated spring loaded check valves and an independently operated spring loaded air inlet valve located on the discharge side of the check or checks. Device includes tightly closing shut-off valves on each side of the check valve and properly located test cocks for the testing of the check valve(s), which is designed to be subject to static line pressure. (K). Reduced Pressure Principle Backflow Preventer - An assembly consisting of two independently operating approved check valves with an automatically operating differential relief valve located between the two check valves, tightly closing shut-off valves on each side of the check valves, plus properly located test cocks for the testing of the check valves and the relief valve. (L) Residential Dual Check - An assembly of two spring loaded, independently operating check valves. Generally employed immediately downstream of the water meter to act as a containment device. (M) Water Service Line - The water conveying piping, valves, fittings, and other appurtenances, including the water meter, which allow the movement of water to or from the water distribution system main.
Added by Ord. No. 7880, 2-15-93
§35-45. Backflow Prevention
Added by Ord. No. 7880, 2-15-93
§35-46. Backflow Protection for Existing Facilities
(A) To be completed no later than December 31, 1994:
(B) To be completed no later than December 31, 1995:
(C) To be completed no later than December 31, 1996:
(D) To be completed no later than December 31, 1997:
(E) To be completed no later than December 31, 1998:
Upon notification by the Utilities Director or Building Department Director in accordance with §35-50, the owner of an affected facility shall have 180 days to complete the required backflow protection measures. If the customer fails to complete protection measures, including submittal of initial certification test results to the Utility Department, within 180 days, the water service line shall be shut off. Added by Ord. No. 7880, 2-15-93
§35-47. Evaluation of Hazard and Backflow Protection Requirements
TABLE 1
TABLE 2
Table Footnotes: 1. For description of assemblies and devices, refer to the Manual of Cross-Connection Control, published by the Foundation for Cross-Connection Control and Hydraulic Research, University of Southern California, Eighth Edition and American Water Works Manual, M-14, Second Edition. Backflow preventers described herein and in the guidelines as "assemblies" must be installed as assemblies keeping the shut-off valves intact. 2. Previous approval by the public water supply system is required for use of a pit or vault (normally prohibited due to possible flooding) or for parallel and bypass installations (normally prohibited without special design considerations and proper cross-connection controls). 3. Backflow preventers shall not be located in any area containing fumes that are toxic, poisonous or corrosive; nor in any area in which they could be damaged by freezing, or by excessively high temperatures or pressures, vibration, physical impact or structural stress; nor knowingly be allowed to conduct highly corrosive or sandy waters without a special testing and maintenance program to assure proper and safe operation. 4. Refer to general and specific installation requirements as stated in the Manual of Cross-Connection Control, Eighth Edition, for conditions or situations not otherwise covered in these regulations. 5. Atmospheric vacuum breakers shall not be subjected to operating pressure for more than 12 hours in any 24-hour period. Hose bibb vacuum breakers are permitted for some uses described in the manual for Cross-Connection Control, Eighth Edition. Garden hose bibbs shall be protected with approved, non-removable or integral, frost-proof, self-draining, anti-siphoning vacuum breakers. 6. Fire protection systems as a minimum shall be equipped with backflow prevention devices as described in AWWA Manual M-14, Second Edition. Backflow preventers under this regulation and connected to fire protection systems shall be considered part of those systems. As such, they shall not be installed, moved, removed, replaced, shut off or in any way altered unless in strict compliance with the rules and regulations promulgated by the State Fire Marshal, and shall be tested and repaired only by authorized fire protection system certified testers. The backflow protection device shall be Underwriters Laboratory listed. Added by Ord. No. 7880, 2-15-93
§35-48. Device Certification
(A) Foundation for Cross-Connection Control and Hydrologic Research, University of Southern California, University Park, Los Angeles, California 90089. (B) American National Standards Institute, 1430 Broadway, New York, New York 10018. (C) Underwriters Laboratories, Inc., 333 Pfingsten Road, Northbrook, Illinois 60062. (D) National Sanitation Foundation, 2355 West Stadium Boulevard, P. O. Box 1468, Ann Arbor, Michigan 48106. (E) International Association of Plumbing and Mechanical Officials, 5032 Alhambra Avenue, Los Angeles, California 90032. Added by Ord. No. 7880, 2-15-93
§35-49. Backflow Inspections
In order to inspect a premise, the inspecting department shall give notice to the customer, setting forth a proposed date and time at least ten (10) working days in advance. If the customer cannot make the premises available for inspection on that date and time, the customer shall contact the Department to arrange another date and time for inspection. If the Department and the customer cannot agree on a date and time for inspection within 30 days of the initial notice, the water service line shall be shut off. All inspections shall be made during normal working hours. Added by Ord. No. 7880, 2-15-93
§35-50. Backflow Prevention; Order Authority
Added by Ord. No. 7880, 2-15-93
§35-51. Appeal of Backflow Prevention Order
Added by Ord. No. 7880, 2-15-93
§35-52. Backflow Preventer; Installation, Maintenance, and Testing
Added by Ord. No. 7880, 2-15-93
§35-53. Customers Responsibility
(A) The customer shall be responsible to cause all backflow, backpressure or back-siphonage protection devices equipped with test ports to be tested as often as required by the Utilities Director, but at least upon initial installation, when repaired, and once each year. All tests shall be done by a Backflow Preventer Test and Repair Technician, Grade VI Water Supply Operator, certified by the State of Nebraska Department of Health. Test results shall be forwarded to the Utilities Director on standard reporting forms. The test report shall be signed by the certified tester, attesting to proper backflow preventer operation. Devices equipped with test ports and installed on lawn sprinkling systems which are supplied with water from a service line equipped with a backflow, backpressure or back siphonage detection device shall be tested upon initial installation, replacement of integral parts, and every fifth year thereafter. (B) Public water supply system consumers are required to assess and report potential backflow hazards on their premises and take any steps necessary for protection of public health and safety as often as reasonably requested by the Utilities Director and which shall be no less often than every five years.
Added by Ord. No.
7880, 2-15-93
§35-54. Backflow Prevention; Penal Provision; Violation; Penalty
Added by Ord. No. 7880, 2-15-93
§35-55 through §35-59 Reserved |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
|
|
This site is optimized for Internet Explorer
4.0 and Netscape Navigator 4.0 browsers.
Click on either of these
hyperlinks to upgrade to the latest versions: |